NORD Drivesystems BU0180 User Manual

Page 150

Advertising
background image

SK 180E Manual for frequency inverters

150

Pre-series version

BU 0180 GB-0914

7.4 Table of possible reasons for the operating status "switch-on disabled"

The following table summarises the messages which are generated if the frequency inverter cannot be
enabled, although no fault is present.

Display

Reason:

Text in the ParameterBox

Cause

Remedy

Group

Details in
P700 [-03]

I000

0.1

Disable voltage from IO

If the function "disable voltage"is parameterised, input (P420
/ P480) is at Low

Set "input high"

Check signal cable (broken cable)

0.2

IO fast stop

If the function "fast stop"is parameterised, input (P420 /
P480) is at Low

Set "input high"

Check signal cable (broken cable)

0.3

Disable voltage from bus

For bus operation (P509): control word Bit 1 "Low"

0.4

Bus fast stop

For bus operation (P509): control word Bit 2 "Low"

0.5

Enable on start

Enable signal (control word, Dig I/O or Bus I/O) was already
applied during the initialisation phase (after manis "ON", or
control voltage "ON").

Only issue enable signal after completion of initialization
(i.e. when the FI is ready)

Activation of "Automatic Start" (P428)

I006

6.0

Charging error

Charging relay not energized, because:

Mains / link voltage too low

Mains failure

Evacuation run activated (parameter (P420) / (P480))

I011

11.0

Analog Stop

If an analog input of the frequency inverter or a connected
IO extension is configured to detect cable breaks (2-10V
signal or 4-20mA signal), the frequency inverter switches to
the status "Not ready for switch-on" if the analog signal
undershoots the value 1V or 2mA.

This also occurs if the relevant analog input is
parameterised to function "0" ("no function").

I014

Reserved