6 information (frequency inverter) – NORD Drivesystems BU0180 User Manual

Page 127

Advertising
background image

6 Parameterisation

BU 0180 GB-0914

Pre-series version

127

6.1.6

Information (Frequency inverter)

Parameter

Setting value / Description / Note

Device

Supervisor

Parameter
set

P700

[-01]

...

[-03]

Actual operating status

(Actual operating status)

0.0 ... 21.4

Display of current messages for the present operating status of the frequency inverter such as
faults, warnings or the reason why switch-on is disabled. For details of the messages, see
Section 7

[-01] = Present fault, shows the currently active (unacknowledged) fault (Section 7.2.1).

[-02] = Present warning, indicates a current warning message (Section 7.3)

[-03] = Reason for disabled starting, indicates the reason for an active start disable

(Section 7.4)

Note

SimpleBox: with the Simplebox only warning messages and faults can be displayed. Display of
the messages is in encoded form. For the description of the codes (warning/error numbers),
please refer to the tables in Sections 7.2.1 and 7.3.

ParameterBox: with the ParameterBox the messages are displayed in plain text. In addition, the
reason for a possible disabling of starting can also be displayed.

Bus: The display of bus-level error messages is made in decimal integer format. If this value is
divided by 10, the display corresponds to that which is listed in Section 7.2.

Example: Display: 20

→ Error number 2.0

P701

[-01]

...

[-05]

Last error 1...5

(Last fault 1...5)

0.0 ... 21.4

This parameter stores the last 5 faults. (Details in Section 7 )

With the SimpleBox the corresponding memory location 1...5 (Array parameter), must be
selected and confirmed with the ENTER key in order to read the stored error code.

P702

[-01]

...

[-05]

Freq. prev. error 1...5

(Frequency previous error 1...5)

S

-400.0 ... 400.0 Hz

This parameter stores the output frequency that was being delivered at the time the fault
occurred. The values of the last 5 errors are stored.

With the SimpleBox, the corresponding memory location 1...5- (Array parameter) must be
selected and confirmed using the OK key to read the stored error code.

P703

[-01]

...

[-05]

Current previous fault 1...5

(Current previous fault 1...5)

S

0.0 ... 999.9 A

This parameter stores the output current that was being delivered at the time the fault occurred.
The values of the last 5 errors are stored.

With the SimpleBox, the corresponding memory location 1...5- (Array parameter) must be
selected and confirmed using the OK key to read the stored error code.

P704

[-01]

...

[-05]

Vltg. previous error 1...5

(Voltage previous error 1...5)

S

0 ... 600 V AC

This parameter stores the output voltage that was being delivered at the time the fault occurred.
The values of the last 5 errors are stored.

With the SimpleBox, the corresponding memory location 1...5- (Array parameter) must be
selected and confirmed using the OK key to read the stored error code.

Advertising