NORD Drivesystems BU0180 User Manual

Page 117

Advertising
background image

6 Parameterisation

BU 0180 GB-0914

Pre-series version

117

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P528

Load monitoring Delay

(Load monitoring Delay)

S

P

0.10 ... 320.00 sec

{ 2.00 }

Parameter (P528) defines the delay time for which an error message ("E12.5") is suppressed on
infringement of the

defined monitoring range ((P525) … (P527)). A warning ("C12.5") is

triggered after half of this time has elapsed.

According to the selected monitoring mode (P529) an error message can also be generally
suppressed.

P529

Load monitoring mode

(Load monitoring mode)

S

P

0 ... 3

{ 0 }

The reaction of the frequency inverter to an infringement of the defined monitoring range
((P525) … (P527)) after the elapse of the delay time (P528) is specified by parameter (P529).

0 = Fault and warning, After the elapse of the time defined in (P528), an infringement of the

monitoring range produces a fault ("E12.5"). A warning ("C12.5") is given after the
elapse of half of this time.

1 = Warning, After the elapse of half of the time defined in (P528) and infringement of the

monitoring range produces a warning ("C12.5").

2 = Err. and warn. in const. "Fault and warning in constant travel", as for setting "0",

however monitoring is inactive during acceleration phases.

3 = Only warning

in

const., "Warning only during constant travel", as for setting

“1”,

however, monitoring is inactive during acceleration phases.

Advertising