6 Parameterisation

BU 0180 GB-0914

Pre-series version

91

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P2xx

Control/characteristic curve parameters

NOTE: "typical"

P211

P210

P204

P201

P216

P215

Output

voltage

Output frequency

Time

Settings for the...

Current vector control (factory setting)

P201 to P209 = Motor data

P210 = 100%

P211 = 100%

P212 = 100%

P213 = 100%

P214 = 0%

P215 = no significance

P216 = no significance

Linear V/f characteristic curve

P201 to P209 = Motor data

P210 = 100% (static boost)

P211 = 0%

P212 = 0%

P213 = no significance

P214 = no significance

P215 = 0% (dynamic boost)

P216 = 0s (time dyn. boost)

P220

Para. identification

(Parameter identification)

P

0... 2

{ 0 }

Duration up to 240 s

The motor data is automatically determined by the FI with this parameter. In most cases this
leads to considerably better drive characteristics, as DC asynchronous motors are subject to
manufacturing tolerances which are not documented on the rating plate.

If unfavorable operating characteristics result, select a suitable motor in P200 or set the
parameters P201 … P208 manually.

0 = No identification

1 = Identification RS: only the stator resistance (display in P208) is determined.

2 = Motor identification: all motor parameters (P202, P203, P206, P208, P209) are

determined.

Procedure:

a) The identification should be made with the motor cold. Warming up of the motor during

operation is automatically taken into account.

b) The FI m

ust be in an “operative condition”‘. For Bus operation, the Bus must be

operating without error. The FI must not be in a state of switch-on block.

c) The motor power may only be one power level greater or 3 power levels lower than the

nominal power of the FI.

d) The motor data should be set according to the rating plate or P200. However, at least

the nominal frequency (P201), the nominal speed (P202), the voltage (P204), the power
(P205) and the motor circuit (P207) should be known.

e) If the identification cannot be concluded successfully, the error message E019 is

generated. See also Section 6, Error messages.

f) Reliable identification can be made with motor cables up 20m in length.


NOTE:

After identification of parameters, P220 is again = 0.

Care must be taken that the connection to the motor is not interrupted during the
entire measuring process.