4 commissioning of the as interface – NORD Drivesystems BU0180 User Manual

Page 72

Advertising
background image

SK 180E Manual for frequency inverters

72

Pre-series version

BU 0180 GB-0914

5.4.4

Commissioning of the AS Interface

Connection

Connection of the AS interface cable is made via terminals 85/85 of the terminal block and can optionally be
made to an appropriately labelled M12 flange plug contact (yellow) Details of the connection terminals are
explained in Section 2.8.2.

Signal status LED / ASi-specific display
With these devices, the status of the ASi interface is indicated by the dual colour LEDAS-i.

LED (dual)

Meaning

OFF

No AS interface voltage to the module (PWR)

Connections to terminals 84 and 85 exchanged.

green ON

Normal operation (AS interface active)

red ON

no exchange of data

 Slave address = 0

 Slave not in LPS

 Slave with incorrect IO/ID

 Master in STOP mode

 Reset active

alternately
flashing
red / green

Peripheral error

 FI control unit does not start (AS-i voltage too low,

control unit faulty)

Control voltage - frequency inverter supply

The yellow ASi cable supplies the AS interface with the necessary control voltage. The control section of the
frequency inverter is not supplied from the AS interface voltage.

Configuration

The most important functions are assigned via the arrays [-

01] … [-04] of parameter (P480) and (P481).

Addressing

In order to use a frequency inverter in an ASi network, this must be assigned with a unique address (1-31).
The FI is set to address 1 as the factory setting, and can therefore be identified as a "new device" by the
AS-i master (prerequisite for the automatic address assignment by the master).

In many other cases, addressing is carried out by means of a normal addressing device for AS-i slaves.
The following should be noted:

85 84

Advertising