6 Parameterisation

BU 0180 GB-0914

Pre-series version

121

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P540

Mode phase sequence

(Mode phase sequence)

S

P

0 ... 7

{ 0 }

For safety reasons this parameter can be used to prevent a rotation direction reversal and
therefore the incorrect rotation direction.

This function does not operate with active position control (P600 ≠ 0).

0 = None, "No restriction of direction of rotation"

1 = Dir key locked, rotation direction change key

of the SimpleBox is locked

2 = CW only*, only clockwise direction is possible. The selection of the "incorrect" rotation

direction leads to the output of the minimum frequency P104 with the
field of rotation R.

3 = CCW only*, only counter-clockwise direction is possible. The selection of the "incorrect"

rotation direction leads to the output of the minimum frequency P104 with the field of
rotation L.

4 = Enable direction only, rotation direction is only possible according to the enable signal,

otherwise 0 Hz.

5 = CW only

monitored, "Only CW rotation monitored *, only CW field direction possible.

The selection of the "incorrect" rotation direction leads to a switch-off (control lock) of
the FI. If necessary, care should be taken that the setpoint (>f

min

) is sufficiently high.

6 = CCW only monitored, "

Only CCW rotation monitored“ *, only CCW field direction

possible. The selection of the "incorrect" rotation direction leads to a switch-off (control
lock) of the FI. If necessary, care should be taken that the setpoint (>f

min

) is sufficiently

high.

7 = Only enable monitored, "Only enabled direction monitored, Rotation direction is only

possible according to the enable signal, otherwise the FI is switched off.


*) Applies for control via keyboard and control terminals.