Setting value / Description / Note

Device

Supervisor

Parameter
set

P412

Setpoint process controller

(Setpoint value for process controller)

S

P

-10.0 ... 10.0 V

{ 5.0 }

Fixed specification of a setpoint for the process controller that will only occasionally be altered.

Only with P400 = 6 or 7 (PID process controller). Further details can be found in Section 9.2 .

P413

P-component PI-controller

(P-component of PI-controller)

S

P

0.0 ... 400.0 %

{ 10.0 }

This parameter is only effective when the function PI controller actual frequency is selected.

The P-component of the PI controller determines the frequency jump if there is a control deviation
based on the control difference.

E.g.: At a setting of P413 = 10% and a rule difference of 50%, 5% is added to the actual setpoint.

P414

I-component PI-controller

(I-component of PI-controller)

S

P

0.0 ... 3,000.0 %/s

{ 10.0 }

This parameter is only effective when the function PI controller actual frequency is selected.

The I-component of the PI controller determines the frequency change, dependent on time.

Note:

In contrast to other NORD series, parameter P414 is smaller by a factor of 100
(Reason: better setting ability with small I-components).

P415

Process controller limit

(Control limit of process controller)

S

P

0 ... 400.0 %

{ 10.0 }

This parameter is only effective when the function PI process controller is selected. This
determines the control limit (%) after the PI controller.

For further details, see Section 9.2.

P416

Ramp time PI setpoint.

(Ramp time PI setpoint value)

S

P

0.00 ... 99.99 sec

{ 2.00 }

This parameter is only effective when the function PI process controller is selected.

Ramp for PI setpoint

P417

[-01]

[-02]

Offset analog output

(Offset analog output)

S

P

-10.0 ... 10.0 V

{ all 0.0 }

[-01] =

First IOE, AOUT of the first I/O extension (SK xU4-IOE)

[-02] =

Second IOE, AOUT of the second I/O extension (SK xU4-IOE)

... only with
SK CU4-IOE or
SK TU4-IOE

In the analog output function an offset can be entered to simplify the processing of the analog
signal in other equipment.

If the analog output has been programmed with a digital function, then the difference between the
switch-on point and the switch-off point can be set in this parameter (hysteresis).

P418

[-01]

[-02]

Analog output function

(Analog output function)

S

P

0 ... 33

{ all 0 }

[-01] =

First IOE, AOUT of the first I/O extension (SK xU4-IOE)

[-02] =

Second IOE, AOUT of the second I/O extension (SK xU4-IOE)