2 basic parameter (frequency inverter) – NORD Drivesystems BU0180 User Manual

Page 80

Advertising
background image

SK 180E Manual for frequency inverters

80

Pre-series version

BU 0180 GB-0914

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P002

Display factor

(Display factor)

S

0.01 ... 999.99

{ 1.00 }

The selected operating value in parameter P001 >Select of display< is multiplied with the
scaling factor in P000 and displayed in >Operating parameter display<.

It is therefore possible to display system-specific operating such as e.g. the throughput quantity

P003

Supervisor code

(Supervisor code)

0 ... 9999

{ 1 }

0 = The Supervisor parameters are not visible. Otherwise, all parameters are visible.

1 = All parameters are visible.

2 = ... 9999, (except 65) only parameters P001 and P003 are visible.

6.1.2

Basic parameter (frequency inverter)

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P100

Parameter set

(Parameter set)

S

0 ... 3

{ 0 }

Selection of the parameters sets to be parameterised. 4 parameter sets are available. All
parameter set-dependent parameters are identified by P.

The selection of the operating parameter set is performed via a digital input or the Bus control.
Switching can take place during operation (online).

Setting

Digital input

function [8]

Digital input

function [17]

LEDs

SimpleBox

0 = Parameter set 1

Low

Low

1

2

1 = Parameter set 2

High

Low

2

1

2 = Parameter set 3

Low

High

1

2

3 = Parameter set 4

High

High

2

1

If enabled via the keyboard (SimpleBox, PotentiometerBox or ParameterBox), the operating
parameter set will match the settings in P100.