7 Status messages

BU 0180 GB-0914

Pre-series version

145

Display in the
SimpleBox

Fault

Text in the ParameterBox

Cause

Remedy

Group

Details in
P700[-01] /
P701

E012

12.0

External watchdog

The Watchdog function is selected at a digital input and the
impulse at the corresponding digital input is not present for
longer than the time set in parameter P460 >Watchdog
time<.

12.1

Motor limit
"Motor switch-off limit"

The drive switch-off limit (P534 [-01]) has triggered.

Reduce load on motor

Set higher value in (P534 [-01]).

12.2

Generator limit
"Generator switch-off limit"

The generator switch-off limit (P534 [-02]) has triggered.

Reduce load on motor

Set higher value in (P534 [-02]).

12.3

Torque limit

Limit from potentiometer or setpoint source has switched off.
P400 = 12

12.4

Current limit

Limit from potentiometer or setpoint source has switched off.
P400 = 14

12.5

Load limit

Switch-off due to overshooting or undershooting of
permissible load torques ((P525) … (P529)) for the time set
in (P528).

Adjust load.

Change limit values ((P525) ... (P527)).

Increase delay time (P528).

Change monitoring mode (P529).

12.8

Analog In minimum

Switch-off due to undershooting of the 0% adjustment value
(P402) with setting (P401) "0-10V with switch-off on error 1"
or "....2"

12.9

Analog In maximum

Switch-off due to overshooting of the 100% adjustment
value (P402) with setting (P401) "0-10V with switch-off on
error 1" or "....2"

E013

13.2

Shut-down monitoring

The slip error monitoring was triggered; the motor could not
follow the setpoint.

Check motor data P201-P209! This data is very important
for the current controller.

Check motor circuit.

Increase setting value for torque limit in P112.

Increase setting value for current limit in P536.

Check deceleration time P103 and extend if necessary

E014

Reserved