3 motor data / characteristic curve parameters – NORD Drivesystems BU0180 User Manual

Page 87

Advertising
background image

6 Parameterisation

BU 0180 GB-0914

Pre-series version

87

6.1.3

Motor data / characteristic curve parameters

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P200

Motor list

(Motor list)

P

0 ... 51

{ 0 }

Adjustment of the motor data from a list for 4-pole IE1 DS standard motors.

By selecting one of the possible digits and pressing the OK key, all motor parameters
(P201…P209) are adjusted to the selected standard power. The basis for the motor data is a
4-pole IE1 DS standard motor

0 = no change "No change to data"

1 = No motor: In this setting, the FI operates without current control, slip compensation and

pre-magnetising time, and is therefore not recommended for motor applications.
Possible applications are induction furnaces or other applications with coils and
transformers. The following motor data is set here:
50.0 Hz / 1500 rpm / 15.0 A / 400 V / 0.00 kW / cos

=0.90 / Star / R

S

0,01

/ I

EMPTY

6.5 A

2 = 0.12 kW 230 V

3 = 0.16 PS 230 V

4 = 0.18 KW 230 V

5 = 0.25 PS 230 V

6 = 0.25 kW 230 V

7 = 0.33 Hp 230 V

8 = 0.25 kW 400 V

9 = 0.33 Hp 460 V

10 = 0.37 kW 230 V

11 = 0.50 Hp 230 V

12 = 0.37 kW 400 V

13 = 0.50 Hp 460 V

14 = 0.55 kW 230 V

15 = 0.75 Hp 230 V

16 = 0.55 kW 400 V

17 = 0.75 Hp 460 V

18 = 0.75 kW 230 V

19 = 1.0 Hp 230 V

20 = 0.75 kW 400 V

21 = 1.0 Hp 460 V

22 = 1.1 kW 230 V

23 = 1.5 Hp 230 V

24 = 1.1 kW 400 V

25 = 1.5 Hp 460 V

26 = 1.5 kW 230 V

27 = 2.0 PS 230 V

28 = 1.5 kW 400 V

29 = 2.0 PS 460 V

30 = 2.2 kW 230 V

31 = 3.0 PS 230 V

32 = 2.2 kW 400 V

33 = 3.0 PS 460 V

34 = 3.0 kW 230 V

35 = 4.0 PS 230 V

36 = 3.0 kW 400 V

37 = 4.0 PS 460 V

38 = 4.0 kW 230 V

39 = 5.0 PS 230 V

40 = 4.0 kW 400 V

41 = 5.0 PS 460 V

42 = 5.5 kW 230 V

43 = 7.5 PS 230 V

44 = 5.5 kW 400 V

45 = 7.5 PS 460 V

46 = 7.5 kW 230 V

47 = 10 PS 230 V

48 = 7.5 kW 400 V

49 = 10.0 PS 460 V

50 = 11.0 kW 400 V

51 = 15.0 PS 460 V

NOTE:

As P200 returns to = 0 after the input confirmation, the control of the set motor can
be implemented via parameter P205.

P201

Nominal motor frequency

(Nominal motor frequency)

S

P

10.0 ... 399.9 Hz

{***}

The motor nominal frequency determines the V/f break point at which the FI supplies the
nominal voltage (P204) at the output.

P202

Nominal motor speed

(Nominal motor speed)

S

P

150 ... 24000 rpm

{***}

The nominal motor speed is important for the correct calculation and control of the motor slip
and the speed display (P001 = 1).

P203

Nominal motor current

(Nominal motor current)

S

P

0.1 ... 300.0 A

{***}

The nominal motor current is a decisive parameter for the current vector control.

*** These settings are dependent on the nominal power of the FI or the selection in parameter P200.

Advertising