3 commissioning examples, 3 kty84-130 connection, Commissioning examples – NORD Drivesystems BU0180 User Manual

Page 68

Advertising
background image

SK 180E Manual for frequency inverters

68

Pre-series version

BU 0180 GB-0914

5.2.3

Commissioning examples

All devices can be operated in the condition in which they are delivered. The standard motor data of a
4-pole IE1 standard asynchronous motor of the same power are parameterised. The PTC input must be
bypassed, if a motor with PTC is not available. Parameter (P428) must be changed if an automatic start-up
with "Mains On" is required.

5.2.3.1

Minimal configuration

The frequency inverter provides all the necessary low voltages (24V DC / 10V DC).

Function

Setting

Setpoint

External 10 kOhm potentiometer

Controller enable

External switch S1

Minimal configuration with options

In order to implement completely autonomous operation (i.e. independent of control cables etc.) a
potentiometer unit (SK CU4-POT) is required. In this way, the required speed and direction control can be
achieved with only a single mains cable (single phase or three-phase, according to the version) (see
connection example in Section 3.3.1).

5.3 KTY84-130 connection

The current vector control of the SK 1x0E series can be further optimised by the use of a KTY84-130
temperature sensor (R

th(0°C)

=500

, R

th(100°C)

=1000

). By continuous measurement of the motor temperature,

the highest precision of regulation by the frequency inverter and the associated optimum speed precision of
the motor is achieved at all times. As the temperature measurement starts immediately after the (mains)
switch-on of the frequency inverter, the frequency inverter provides immediate optimum control, even if the
motor has a considerably increased temperature after an intermediate "Mains off / Mains on" of the
frequency inverter.

Connection examples:
SK 1x0E

Connection of a KTY-84 to either of the two analog inputs of the SK 1x0E is possible. In the following examples,
analog input 2 of the frequency inverter is used.

1. The motor data P201-P207 must be set according to the rating plate.

2. The motor stator resistance P208 is determined at 20°C with P220 = 1.

3. Function analog input 2, P400 [-02] = 30 (Motor temperature)

4. The mode analog input 2 P401 [-06] = 1 (negative temperatures are

also measured)

Adjustment of analog input 2: P402 [-06] = 1.54V and
P403 [-06] = 2.64V (with R

V

= 2.7 kOhm)

5. Adjust time constants: P404 [-02] = 400ms

(Filter time constant is maximum)

6. Motor temperature control (display): P739 [-03]

* If necessary, also Terminal 40





Frequency inverter
SK 1x0E-...

Co

ntro

l terminal b

ar

12/40

14

11

.

43

.

21
22

.

38
39

L1 - L2/N - L3

230/400 V

1/3~ 230/400V + PE



Switch S1



Motor PTC



Potentiometer

10kOhm