2 control connection details – NORD Drivesystems BU0180 User Manual

Page 36

Advertising
background image

SK 180E Manual for frequency inverters

36

Pre-series version

BU 0180 GB-0914

2.8.2

Control connection details

The frequency inverter generates its own control voltage and provides this to Terminal 43.

Terminal/

Designation

Function

{Factory setting}

Data

Description / wiring suggestion

Parameter

43

VO/24V

24V supply

Output

24V DC ±25%

max. 150 mA

1

(output)

Voltage supply provided by the FI
for control of the digital inputs

-

40 GND / 0V

Reference potential
for digital signals

-

21

DIN1

Digital input 1

{ON right}

Digital input as per
EN 61131-2 Type 1

Low: 0

-5 V

(~ 9.5 k

Ω)

High: 15-30 V

(~ 2.5-3.5 k

Ω)

Input capacitance:
Input 1…3 = 10 nF

Scan time: 1 ms

Reaction time:

≥ 4 ms

Input 1 reacts slowly

Inputs 2 + 3 react quickly

P420 [01]

22

DIN2

Digital input 2

{ON left}

P420 [02]

23

DIN3

Digital input 3

{fixed frequency 1,
(P465[-01])}

P420 [03]

1

DOUT1

Output 1

{Fault}

Digital output

24V DC, max. 20 mA

For inductive loads:
provide protection with a
free-wheeling diode.

For evaluation in a control system.

P434 [01]

3

DOUT2

Output 2

{Fault}

P434 [02]

14

AIN1 +

Analog input 1

{Setpoint frequency}

U=0…10 V, R

i

=30

Resolution 12Bit

I=0/4

…20 mA,

burden resistor (250

Ω)

via DIP switch S1 can be
switched to AIN1/2

11

12

14

16

R=10k

Matching of the analog signals is
performed via P402 and P403.

P400 [01]

16

AIN2 +

Analog input 2

{No function}

P400 [02]

12 AGND / 0V

Reference potential
for analog signals

0 V analog

11

10V REF

+10 V
Reference voltage

+10 V, 5 mA

38

TF+

PTC resistor input

-

For monitoring motor temperature
with PTC

A shielded cable must be used for
separate mounting of the motor
and the FI (note the cable length).

-

39

TF-

PTC resistor input

1

The current which is drawn from the digital outputs must also be covered by this. Any control modules which are

connected to the RJ12 socket also place a load on the 24V supply. (150mA = I

DIG1

+ I

DIG2

+ I

OUT

+ I

CONTROL

)

Advertising