NORD Drivesystems BU0180 User Manual

Page 144

Advertising
background image

SK 180E Manual for frequency inverters

144

Pre-series version

BU 0180 GB-0914

Display in the
SimpleBox

Fault

Text in the ParameterBox

Cause

Remedy

Group

Details in
P700[-01] /
P701

E010

10.0

Bus Timeout

(Telegram time-out /
Bus off 24V int. CANbus)

Data transfer is faulty. Check P513.

Check physical bus connections.

Check bus protocol program process.

Check Bus Master.

Check 24V supply of internal CAN/CANopen Bus.

Nodeguarding error (internal CANopen)

Bus Off error (internal CANbus)

10.2

Bus Timeout Option

(Telegram timeout)

Telegram transfer is faulty.

Check physical connections.

Check bus protocol program process.

Check Bus Master.

10.4

Init error Option

(Initialisation error in bus
module)

Check Bus module current supply.

DIP switch setting of a connected I/O extension module is
incorrect

10.1

System error option

(Bus module)

Further details can be found in the respective additional
BUS operating instructions.

I/O extension:

Incorrect measurement of the input voltage or undefined
provision of the output voltage due to error in reference
voltage generation.

Short circuit at analog output

10.3

10.5

10.6

10.7

10.9

Module missing / P120

The module entered in parameter (P120) is not available.

E011

11.0

Customer interface

(AnalogDigital converter error)

Internal customer unit (internal databus) faulty or damaged
by radio radiation (EMC)

Check control terminals connection for short-circuit.

Minimize EMC interference by laying control and power
cables separately.

Device and shielding must be well earthed.