2 Modules

BU 0060 GB-4112

17

2.1.2 CANnord / CANopen, internal RJ45 connection (SK 511E and above)

With SK 511E and above, a CANnord/CANopen interface is
integrated and can be accessed via RJ45 connections.

To use the CANnord/CANopen, the bus must be provided with an
external 24V voltage supply. The CAN participant can therefore
be identified by the master system even without a voltage supply
to the frequency inverter.

Information

Control voltage

There is no internal coupling between the control voltage level of the frequency inverter and the bus system.

CANnord (P509 = 3)

CANopen (P509 = 6)

Baud rate (P514)

The baud rate is set in the frequency inverter parameter P514. Transfer
rates of up to 500 kbit/s can be used. (Optionally up to 1 Mbit/s)

Supply voltage

The supply voltage is 24V DC

±25% (pin 8 = 24V, pin 7 = GND, approx.

30mA) and is connected via the RJ45 connector.

Termination resistor

The termination resistor R=120

W for the last bus participant is located

next to the BUS connection. Switch No. 2 = ON.

BUS address (P515)

The BUS address is set in the frequency inverter parameter P515.

0…255

0…127

BUS connection

2x RJ45 sockets are connected in parallel internally.

Table 2: Details of SK 5xxE – BUS -configuration via RJ45