CANopen – Supplementary manual options for NORD - Frequency Inverters

40

BU 0060 GB-4112

4.1.2 Control word (STW)

The control word (STW) is the first word transferred to the frequency inverter in the process data area
in an order telegram. For example, a control word "Ready for switch-on" corresponds to 047E

(hex)

. In

general the command "Standby" should be the first command which is transferred to the inverter.

Bit

Valu
e

Meaning

Remarks

0

0

Not ready for operation

Reverse with the brake ramp, with disconnection from supply at f=0Hz (OFF1)

1

Ready for operation

Frequency inverter ready for operation

1

0

Disable voltage

Cut off voltage; the inverter output voltage is switched off; the FI enters a state
where switching on is disabled. (OFF2)

1

Do not disable voltage

Operating condition OFF 2 is cancelled

2

0

Emergency Stop active

Quick stop with programmed quick stop time; with disconnection from supply at
f=0Hz; the FI switches to starting disabled condition (OFF3).

1

Emergency Stop not
active

Operating condition OFF 3 is cancelled

3

0

Disable operation

Cut off voltage; the inverter output voltage is switched off; the FI enters a state
where switching on is enabled.

1

Enable operation

The output voltage is enabled; ramp to the existing setpoint

4

0

Pulse not enabled

Ramp generator is set to zero; no disconnection from supply at f=0Hz; FI remains
in the operation enabled state.

1

Enable pulses

Enable ramp generator

5

0

Ramp not enabled

The setpoint currently provided by the ramp generator is "frozen" (frequency is
maintained).

1

Enable ramp

Enable setpoint on ramp generator

6

0

Setpoint not enabled

Selected setpoint value is set to zero on the ramp generator.

1

Enable setpoint

Selected ramp generator setpoint is activated.

7

0

No acknowledgement

With the switch from 0 to 1, errors which are no longer active are acknowledged.

1

Acknowledge error
(0

à1)

Note: If a digital input has been programmed for the "ack.fault" function, this bit
must not permanently be set to 1 via the bus (otherwise, flank evaluation would
be prevented).

8

0

1

Start function 480, 11

Bus bit 8 from the control word is set. Only for SK 2xxE and SK 5xxE. For further
details of the function please refer to parameter P480.

9

0

1

Start function 480, 12

Bus bit 9 from the control word is set. Only for SK 2xxE and SK 5xxE. For further
details of the function please refer to parameter P480.

10

0

Control data invalid

The transmitted process data is invalid.

1

Control data valid

Valid process data is transferred from the master.
Note: In order for the transmitted setpoint to be valid, this bit must also be set
(setting: interface), even if only setpoint values are transmitted via the bus.

11

0

1

Rotation right is on

Rotational direction right (priority) ON*

12

0

1

Rotation left is on

Rotational direction left ON*

13

0/1

Reserved

Reserved

14

0/1

Parameter set Bit 0 ON

00 = Parameter set 1
01 = Parameter set 2

10 = Parameter set 3
11 = Parameter set 4

15

0/1

Parameter set Bit 1 ON

* If Bit 12=0, then "Direction of rotation right ON" applies

Table 7: Control word (STW)