5.1 BUS parameter data for SK 300E/700E/750E

Pos : 110 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ P4xx St euer klemmen @ 0\ mod_1327678262854_388. doc x @ 9027 @ 5 @ 1

5.1.1 Control terminals

Parameter
{factory setting}

Setting value / Description / Note

Supervisor

Parameter
set

Pos : 111 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P480 – Funkti on Bus I/O I n Bits [SK 300E, SK 700E] @ 1\ mod_1335776613691_388. doc x @ 24730 @ @ 1

P480

[-01]

...

[-08]

Function BusIO In Bits

(Function Bus I/O In Bits)

S

0 ... 62

{ all 0 }

The Bus I/O In Bits are perceived as digital inputs. They can be set to the same functions
(P420...425).

In order to use this function, one of the bus setpoints (P546, P547, P548) must be set to >Bus I/O
In Bits 0-7 <. The required function must then be assigned to the relevant bit.

[-01] = Bus I/O In Bit 0

[-02] = Bus I/O In Bit 1

[-03] = Bus I/O In Bit 2

[-04] = Bus I/O In Bit 3

[-05] = Bus I/O In Bit 4

[-06] = Bus I/O In Bit 5

[-07] = Bus I/O In Bit 6

[-08] = Bus I/O In Bit 7

The possible functions for the Bus In Bits can be found in the table of functions for the digital
inputs P420...425.

Note

ControlBox at SK 300E

SK 300E: Only the value of the first array can be accessed with the ControlBox. A
ParameterBox or the NORDCON software is required to access the other arrays.

Pos : 112 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P481 – Funkti on Bus I/O O ut Bits [ SK 300E, SK 700E] @ 1\ mod_1335777244985_388.doc x @ 24754 @ @ 1

P481

[-01]

...

[-08]

Function BusIO Out Bits

(Function Bus I/O Out Bits)

S

0 ... 38

{ all 0 }

The bus I/O Out bits are perceived as digital outputs. These can be set to the same functions as
P434 … P443; P624 … P629 (only SK 7x0E with POSICON).

In order to use this function, one of the bus setpoints (P543, P544, P545) must be set to >Bus I/O
In Bits 0-7 <. The required function must then be assigned to the relevant bit.

[-01] = Bus I/O Out Bit 0

[-02] = Bus I/O Out Bit 1

[-03] = Bus I/O Out Bit 2

[-04] = Bus I/O Out Bit 3

[-05] = Bus I/O Out Bit 4

[-06] = Bus I/O Out Bit 5

[-07] = Bus I/O Out Bit 6

[-08] = Bus I/O Out Bit 7

The possible functions for the Bus Out Bits can be found in the table of functions for the digital
outputs or the relays P434.

Note

ControlBox at SK 300E

SK 300E: Only the value of the first array can be accessed with the ControlBox. A
ParameterBox or the NORDCON software is required to access the other arrays.