5 Parameters

BU 0060 GB-4112

83

P543

Actual bus value 1

(Actual bus value 3)

S

P

0 ... 24

{ 1 }

The return value 1 can be selected for bus actuation in this parameter.

The possible analog functions can be found in the following table.

NOTE:

For further details please refer to the manual for the frequency inverter (P418, P543),

the relevant BUS operating instructions or BU 0510.

Pos : 152 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P543 – Bus-Ist wert e [ SK 54xE] @ 0\ mod_1328097636349_388. doc x @ 11847 @ @ 1

P543

[-01]

...

[-05]

Bus actual value

(Bus – Actual value)

S

P

0 ... 57

{ [-01] = 1 }
{ [-02] = 4 }
{ [-03] = 9 }
{ [-04] = 0 }
{ [-05] = 0 }

In this parameter the return value for bus actuation can be selected.

NOTE:

The actual values 4 and 5 must be supported by the relevant bus module. For
further details please refer to the manual for the frequency inverter (P418, P543),
the relevant BUS operating instructions or the manuals BU 0510 / BU0550.

[-01] = Bus - Actual value 1

[-02] = Bus - Actual value 2

[-03] = Bus - Actual value 3

[-04] = Bus - Actual value 4

[-05] = Bus - Actual value 5

0 =

Off

13 = ... 16 Reserved

1 =

Actual frequency

17 = Value analog input 1

2 =

Actual speed

18 = Value analog input 2

3 =

Current

19 = Setpoint frequency master

value(P503)

4 =

Torque current (100% = P112)

20 = Setpoint frequency master value after

ramp "Setpoint frequency master
value after ramp"

5 =

Digital IO status

4

21 = Act. freq. without slip master value

"Actual frequency without slip master
value"

6 =

... 7 Reserved

22 = Speed encoder 


(only possible with

SK 520E and encoder feedback)

8 =

Setpoint frequency

23 = Actual frequency with slip, "Actual

frequency with slip"

(SW V2.0 and above)

9 =

Error number

24 = Master value, actual freq. with slip,

"Master value, actual freq. with slip"

(SW V2.0 and above)

10 = ... 11 Reserved

53 = ... 57 Reserved

12 = BusIO Out Bits 0...7

Pos : 153 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P544 – Bus-Ist wert 2 [SK 500. .. 535E] @ 0\ mod_1328097766412_388.doc x @ 11870 @ @ 1

P544

Actual bus value 2

(Actual bus value 2)

S

P

0 ... 24

{ 0 }

This parameter is identical to P543.

Condition is PPO 2 or PPO 4 type (P507).

Pos : 154 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P545 – Bus-Ist wert 3 [SK 500. .. 535E] @ 0\ mod_1328097880052_388.doc x @ 11893 @ @ 1

4

The assignment of the digital inputs in P543/ 544/ 545 = 5

Bit 0 = DigIn 1

Bit 1 = DigIn 2

Bit 2 = DigIn 3

Bit 3 = DigIn 4

Bit 4 = DigIn 5

Bit 5 = DigIn 6 (SK 520E and above)

Bit 6 = DigIn 7 (SK 520E and above)

Bit 7 = Dig. func. AIN1

Bit 8 = Dig. func. AIN1 AIN2

Bit 9 = DigIn 8 (SK 540E and above)

Bit 10 = DigIn 1, 1.IOE (SK 540E and above)

Bit 11 = DigIn 2, 1.IOE (SK 540E and above)

Bit 12 = Out 1/ MFR1

Bit 13 = Out 2/ MFR2

Bit 14 = Out 3/ DOUT1 (SK 520E and above)

Bit 15 = Out 4/ DOUT2 (SK 520E and above)