Cancelling of parameter communication (sdo), Table 17: loading parameter data via sdo, Table 19: error codes – parameter communication – NORD Drivesystems BU0060 User Manual

Page 62

Advertising
background image

CANopen – Supplementary manual options for NORD - Frequency Inverters

62

BU 0060 GB-4112

Example: Read out parameter P102, Response: P102, 1.03s

Control byte/

Status byte

Index

Sub-index

Data

Byte 0

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Requirement

0x40

0x20

0x66

0x01

0x00

0x00

0x00

0x00

Response

0x4B

0x20

0x66

0x01

0x67

0x00

0x00

0x00

The control byte

à states the order:

0x40 =

Load value

Response
0x4B =
0x43 =
0x80 =


Deliver the 16 bit value which has been read out
Deliver the 32 bit value which has been read out
Response to an incorrect order

Table 17: Loading parameter data via SDO

Pos : 100 /Anleit ungen/El ektr oni k/Buss yst eme/ 4. Kommuni kati on und Pr ot okoll + Pr ozessdat entransf er/C ANopen [BU0060] /Das CAN open ProtokollAbbruc h der Paramet erkommuni kati on (SD O) [CANopen] @ 1\ mod_1342434882348_388. doc x @ 32420 @ 5 @ 1

Cancelling of parameter communication (SDO)

If problems occur during parameter communication (e.g. value range overflow), a cancel telegram is
sent. This can be recognised by the number 0x80 in byte 0. The cause of the cancellation is indicated
in bytes 4 to 7.

Control

byte

Last index used

Error code

Byte 0

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

0x80

0x00

0x18

0x01

0x02

0x00

0x01

0x06

Table 18: Error message (0x06010002 = attempted writing access to a read-only object)

Error code

Description

0x0601 0001

Access to write-only parameter

0x0601 0002

Access to read-only object

0x0607 0010

Data type or parameter length do not match

0x0609 0030

Parameter value range overflow

0x0609 0031

Parameter value range overflow

0x0609 0032

Parameter value range undershot

0x0609 0011

Sub-Index of parameter does not exist

Table 19: Error codes – Parameter communication