4 Communication and Protocol

BU 0060 GB-4112

59

Information

NORD frequency inverters support dynamic mapping and dummy mapping!

Pos : 91 /Anl eitungen/ Elektroni k/ Bus s yst eme/4. Kommuni kati on und Prot okoll + Proz ess datentr ans fer /CAN open [ BU 0060]/D as C ANopen Pr ot okoll/ PDO- Mappi ng SK 300E, SK 5xxE (SK TU 3-...), SK 700E, SK 750E [CAN open] @ 1\ mod_1342098845033_388. doc x @ 32144 @ 6 @ 1

PDO mapping SK 300E, SK 5xxE (SK TU3-…), SK 700E, SK 750E

PDO type

Length

Identifier

1st word

2nd word

3rd word

4th word

PDO1 (Tx)

4 Byte

180h + NODE-ID

ZSW

IW1

PDO1 (Rx)

4 Byte

200h + NODE-ID

STW

SW1

PDO2 (Tx)

8 Byte

280h + NODE-ID

ZSW

IW1

IW3 *

IW2 *

PDO2 (Rx)

8 Byte

300h + NODE-ID

STW

SW1

SW3 *

SW2 *

PDO3 (Tx)

8 Byte

380h + NODE-ID

ZSW

IW1 (32 Bit)

IW2

PDO3 (Rx)

8 Byte

400h + NODE-ID

STW

SW1 (32Bit)

SW2

PDO4 (Tx)

2 Byte

480h + NODE-ID

ZSW

PDO4 (Rx)

2 Byte

500h + NODE-ID

STW

*) In the SK 5xxE devices, the IW/SW 3/2 are assigned inversely to the words.

3rd word = IW/SW2, 4th word = IW/SW3

In the default setting, all receive PDOs are active. A decision is made when sending messages to the
applicable identifier whether one setpoint or up to three setpoints can be evaluated.

With transmit PDOs, only PDO 1 is active, while PDOs 2 to 4 are deactivated. If the application
requires the sending of several actual values, the corresponding PDO must be switched on. In the
following example, transmit PDO 2 is activated, the default setting transmits a status word and three
actual values. For this, the following messages must be sent via the SDO parameter channel (see
Section 4.3.4):

· Set the NMT status machine for the inverter to the state "Pre-Operational"
· Deactivate PDO 1 à SDO telegram (Index=0x1800 / Subindex=1 / Data=0xc0000181)
· Activate PDO 2 à SDO telegram (Index=0x1801 / Subindex=1 / Data=0x40000281)
· Set the NMT status machine for the inverter to the state "Operational"
· PDO 1 is deactivated to prevent the bus load from rising unnecessarily. The PDO is

activated/deactivated via Bit 31 in the corresponding parameter.

Pos : 92 /Anl eitungen/ Elektroni k/ Bus s yst eme/4. Kommuni kati on und Prot okoll + Proz ess datentr ans fer /CAN open [ BU 0060]/D as C ANopen Pr ot okoll/ PDO- Mappi ng SK 511E bis SK 535E über i nt ernen RJ45 Ansc hluss [C ANopen] @ 1\mod_1342099915579_388. doc x @ 32168 @ 6 @ 1

PDO mapping, SK 511E up to SK 535E via internal RJ45 connection

PDO type

Length

Identifier

1st word

2nd word

3rd word

4th word

PDO1 (Tx)

8 Byte

180h + NODE-ID

ZSW

IW1

IW2

IW3

PDO1 (Rx)

8 Byte

200h + NODE-ID

STW

SW1

SW2

SW3

PDO2 (Rx)

4 Byte

300h + (NODE-ID +1)

IW1 (32 Bit) of an

absolute encoder