1 status via parameter display, Module status of the technology unit, Status via parameter display – NORD Drivesystems BU0060 User Manual

Page 91: Table 26: cannord/canopen status, parameter p748, 6 operating status messages

Advertising
background image

6 Operating status messages

BU 0060 GB-4112

91

6.1.1 Status via parameter display

Module status of the technology unit

In parameter P746, the status of the CANopen technology unit can be read.

For the SK 700E, parameter P746 is a sub-index parameter. The status of the CANnord / CANopen
technology unit (SK TU1-…) is shown in sub-index 0 (or Array -01), the status of the CANnord
customer interface (SK CU1-…) is shown in sub-index 1 (or Array -02).

The parameter contains binary coded information which is displayed in hexadecimal:

15 14 13 12 11 10

9

8

7

6

5

4

3

2

1

0

Module ID

CANopen=0C

hex

Module ready

Module in status “operational”

Initialisation active

Reserved (0)

Module error

Timeout error

Initialisation error (0)

Reserved (0)

Status of internal CANnord/CANopen, SK 511E and above

If the internal RJ45 CANnord/CANopen iterface (SK 511E and above) is used, parameter P748 array -
01 can be used to display the status of the device.

The display is coded in hexadecimal, the individual bits are listed below:

Bit

Meaning

0

1 = 24V Bus supply voltage

1

1 = CAN Bus in "Bus Warning" status

2

1 = CAN Bus in "Bus Off" status

3 – 5

Vacant

6

The protocol of the CAN module is:
0 = CAN

1 = CANopen

7

Vacant

8

1 = "Bootsup Message" sent

9 – 10

CANopen NMT State

Status

Bit 10

Bit 9

Stopped

0

0

Pre-Operational

0

1

Operational

1

0

11 – 15

Reserved

Table 26: CANnord/CANopen status, parameter P748