Error messages if the order cannot be executed, Sub-index (ind) – NORD Drivesystems BU0060 User Manual

Page 54

Advertising
background image

CANopen – Supplementary manual options for NORD - Frequency Inverters

54

BU 0060 GB-4112

Error messages if the order cannot be executed

In the response label "Order cannot be executed" (AK = 7), then an error message is added to the
parameter value (PWE2) of the inverter response. For the meanings of the values transferred, please
refer to the following table.

AK

Meaning

0

Invalid parameter number

1

Parameter value cannot be changed

2

Lower or upper value limit exceeded

3

Incorrect sub-index

4

No array

5

Invalid data type (at present only for SK 700E)

6

Only resettable (only 0 may be written)

7

Description element cannot be changed

9

Description data not present

201

Invalid order element in the last order received

202

Internal response label cannot be depicted

Pos : 83 /Anl eitungen/ Elektroni k/ Bus s yst eme/4. Kommuni kati on und Prot okoll + Proz ess datentr ans fer /CAN open [ BU 0060]/D as C ANnord Pr ot okoll /Subi ndex (IND) [C AN] @ 2\ mod_1347286573347_388. doc x @ 44391 @ 5 @ 1

Sub-index (IND)

1

2

3

4

PKE

IND

PWE1

PWE2

15

14

13

12 11

10

9

8

7

6

5

4

3

2

1

0

No information / all 0

P1-P4

Array 1-64

P1-P4

Sub-index

The structure and function of the parameter index (IND) depends on the type of parameter to be
transferred. For values which depend on the parameter set, the parameter set can be selected via Bits
0 and 1 of the Index (IND) (0 = parameter set 1, 1 = parameter set 2,...).

If the parameter to be processed is also an array parameter (e.g. position array for the POSICON
option), then the sub-index of the required parameter can additionally be accessed via Bit 2 to Bit 7 of
the sub-index (0 = array element 1, 1 = array element 2,…):

Array element

Parameter set

Index

5 (000101

BIN

)

2 (01

BIN

)

15

HEX

= 0001 0101

BIN

21 (010101

BIN

)

4 (11

BIN

)

57

HEX

= 0101 0111

BIN

If a parameter is not dependent on the parameter set, then Bits 0 -7 are used for the sub-index.

Please refer to the operating instructions for details of the structure of the individual parameters and
which values may be called up.

If the sub-index is used, nos. 6, 7, 8 or 11, 12 must be used as the order label, in order for the
sub-index to be effective.

Pos : 84 /Anl eitungen/ Elektroni k/ Bus s yst eme/4. Kommuni kati on und Prot okoll + Proz ess datentr ans fer /CAN open [ BU 0060]/D as C ANnord Pr ot okoll /Paramet er- Wert ( PWE) [CAN] @ 2\mod_1347287056551_388. doc x @ 44416 @ 5 @ 1