Inhibit time, Event timer, Pdo settings – NORD Drivesystems BU0060 User Manual

Page 60: Id node x id sende - + = - 600 0, Id node x id empfangs - + = - 580 0

Advertising
background image

CANopen – Supplementary manual options for NORD - Frequency Inverters

60

BU 0060 GB-4112

PDO mapping, SK 540E up to SK 545E via internal RJ45 connection

PDO type

Length

Identifier

1st word

2nd word

3rd word

4th word

PDO1 (Tx)

8 Byte

180h + NODE-ID

ZSW

IW1

IW2

IW3

PDO1 (Rx)

8 Byte

200h + NODE-ID

STW

SW1

SW2

SW3

PDO2 (Tx)

5 Byte

280h + NODE-ID

IW4

IW5

PDO2 (Rx)

5 Byte

300h + NODE-ID

SW4

SW5

PDO3 (Rx)

4 Byte

400h + (NODE-ID +1)

IW1 (32 Bit) of an

absolute encoder

Pos : 94 /Anl eitungen/ Elektroni k/ Bus s yst eme/4. Kommuni kati on und Prot okoll + Proz ess datentr ans fer /CAN open [ BU 0060]/D as C ANopen Pr ot okoll/ Inhibi t Ti me [C ANopen] @ 1\ mod_1342432696269_388.doc x @ 32299 @ 5 @ 1

Inhibit Time

Each transmit PDO has a parameter "Inhibit Time" (0x1800 – 0x1803 Sub-Index 3). This can be used
to set a minimum send interval between two PDO messages. In networks with numerous subscribers,
the bus load can be influenced with this value. The default setting is 10 ms (Value x 100µs).

Pos : 95 /Anl eitungen/ Elektroni k/ Bus s yst eme/4. Kommuni kati on und Prot okoll + Proz ess datentr ans fer /CAN open [ BU 0060]/D as C ANopen Pr ot okoll/ Event Ti mer [C ANopen] @ 1\ mod_1342432843212_388. doc x @ 32323 @ 5 @ 1

Event Timer

The Parameter Event Time (0x1800 – 0x1803 Subindex 5) can be used for all transmit PDOs. Once
this value is exceeded, the PDOs are transmitted cyclically. The default setting is 250 ms (Value x
1ms).

Pos : 96 /Anl eitungen/ Elektroni k/ Bus s yst eme/4. Kommuni kati on und Prot okoll + Proz ess datentr ans fer /CAN open [ BU 0060]/D as C ANopen Pr ot okoll/ Einst ellungen am PD O [C AN open] @ 1\ mod_1342431680963_388.doc x @ 32251 @ 5 @ 1

PDO settings

All settings for the PDOs are implemented via the SDO parameter channel (Section 4.3.4).

The settings made are not stored permanently in the device, i.e. a reset of the 24 V power supply will
reset the changed parameters to the default values.

Pos : 97 /Anl eitungen/ Elektroni k/ Bus s yst eme/4. Kommuni kati on und Prot okoll + Proz ess datentr ans fer /CAN open [ BU 0060]/D as C ANopen Pr ot okoll/ Parametrier ung i m M ode C AN open (SD O Kommuni kati on) [CAN open] @ 1\ mod_1342433191459_388. doc x @ 32347 @ 3 @ 1

4.3.4 Parameterisation in CANopen mode (SDO communication)

Access to all parameters of the frequency inverter and the CANopen Box is implemented via so-called
service data objects (SDO). Access is via handshake between client and server, i.e. after a message
is transmitted, the response must be waited for before a new message can be sent.

Transmit and receive addresses for SDO access seen from the PLC

ID

Node

x

ID

Sende

-

+

=

-

600

0

ID

Node

x

ID

Empfangs

-

+

=

-

580

0

The Node ID of the frequency inverter is set via the "ID-H" and "ID-L" switches on the CANopen Box
or in the PGM mode via parameter P515.