5 parameters, P748, Status canopen – NORD Drivesystems BU0060 User Manual

Page 89

Advertising
background image

5 Parameters

BU 0060 GB-4112

89

P748

[-01]

...

[-03]

Status CANopen

(CANopen status)

SK 520E or

higher

S

0000 ... FFFF (hex) [01] = CANbus/CANopen status

[-02] = reserved

[-03] = reserved

Bit 0 = 24V bus voltage supply
Bit 1 = CANbus in "Bus Warning" status
Bit 2 = CANbus in "Bus Off" status
Bit 3 ... Bit 5 = free
Bit 6 = Protocol of the CAN module is 0 =

CAN or 1 = CANopen

Bit 7 = free
Bit 8 = "Bootsup Message" sent
Bit 9 = CANopen NMT State
Bit 10 = CANopen NMT State
Bit 11 = free
Bit 12 ... 14 = reserved
Bit 15 = free



CANopen NMT State Bit 10

Bit 9

Stopped =

Pre-Operational =

Operational =

0
0
1

0
1
0