P741, Process data bus out, P745 module version – NORD Drivesystems BU0060 User Manual

Page 88: P746 module status

Advertising
background image

CANopen – Supplementary manual options for NORD - Frequency Inverters

88

BU 0060 GB-4112

P741

[-01]

...

[-23]

Process Data Bus Out

(Process data Bus Out)

S

0000 ... FFFF (hex)

This parameter provides
information about the actual
status word and the actual
values that are transferred
via the bus systems.

[-01] = Status word

Status word, source from
P509.

[-02] = Actual value 1 (P543 [-01])
[-03] = Actual value 2 (P543 [-02])
[-04] = Actual value 3 (P543 [-03])
[-05] = Actual value 4 (P543 [-04])
[-06] = Actual value 5 (P543 [-05])

[-07] = Bus I/O Out Bit (P481)

The displayed value depicts
all Bus OUT Bit sources linked
with "OR".

[-08 ] = Parameter data Out 1
[-09 ] = Parameter data Out 2
[-10 ] = Parameter data Out 3
[-11 ] = Parameter data Out 4
[-12 ] = Parameter data Out 5

Data during parameter
transfer.

[-13] = Actual value 1 master

function

[-14] = Actual value 2 master

function

[-15] = Actual value 3 master

function

[-16] = Actual value 4 master

function

[-17] = Actual value 5 master

function

Actual value of master
function P502 / P503.

[-18] = PLC status word

Status word via PLC

[-19] = Actual value 1 PLC
[-20] = Actual value 2 PLC
[-21] = Actual value 3 PLC
[-22] = Actual value 4 PLC
[-23] = Actual value 5 PLC

Actual value data via PLC

Pos : 167 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P745 – Baugruppen Versi on @ 0\ mod_1328178182499_388. doc x @ 13474 @ @ 1

P745

Module version

(Module version)

-3276.8 ... 3276.8

Version status (software version) of the technology unit (SK TU3-xxx), but only when own
processor is present, i.e. not for SK TU3-CTR.

Have this data available if you have a technical query.

Pos : 168 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P746 – Baugruppen Z ust and PBR [ SK 5xxE] @ 1\ mod_1335793579623_388.doc x @ 25168 @ @ 1

P746

Module status

(Module status)

S

0000 ... FFFF (hex)

Shows the actual status (readiness, error, communication) of the technology unit (SK TU3-xxx),
but only when own processor is present, i.e. not for SK TU3-CTR.

Example:

0603

hex

High byte = 06

hex

à Profibus

Low byte = 03

hex

à Module ready + connection to master

Details of the codes specific to the bus can be found in the section "Error monitoring" of the
relevant supplementary instructions.