7 Examples
BU 0060 GB-4112
95
7. Examples
Various examples are shown below to clarify the control and parameterisation of the frequency
inverter with the bus system.
Pos : 177 /Anleit ungen/El ektr oni k/Buss yst eme/ 7. Beis piel- T elegramme/N etz einschalt en [C ANopen BU 0060] @ 1\ mod_1342785004232_388. doc x @ 35839 @ 25 @ 1
7.1 Mains switch-on
After the CAN participant has been switched on it logs into the system with the CAN ID: 700
hex
+ Node
ID.
Example
Node ID: 50
dec
à 32
hex
Mains On
à if the participant was recognised 732
hex
is transmitted.
As no valid telegram was sent at this time, the inverter switches to the status "Starting disabled" (
à
status word: 0B40).
Pos : 178 /Anleit ungen/El ektr oni k/Buss yst eme/ 7. Beis piel- T elegramme/ Operational setzen der Bus Teilnehmer [CAN open BU0060] @ 1\ mod_1342786735533_388.doc x @ 35863 @ 2 @ 1
7.2 Operational settting of the bus participant
Be sending 0001 to ID000 all participants are set to "Operational".
Pos : 179 /Anleit ungen/El ektr oni k/Buss yst eme/ 7. Beis piel- T elegramme/ Proz ess daten ( PDO) [CAN open BU0060] @ 1\mod_1342776486166_388.doc x @ 35815 @ 2555 @ 1
7.3 Process data (PDO)
The exchange of process data is carried out via PDOs and is illustrated in the following example.
Example:
Communication via:
Technology unit SK TU4-CAO
Scope of data:
STW and SW1
Communication settings on the frequency inverter
Parameter number
Parameter name
Setting
Meaning
P509
Setpoint source
6 or 17
CANopen
P510
Setpoint source
0
Auto
P515 (or rotary
coding switch on
the bus module)
CAN address
(Node ID)
50
(50
dec
= 32
hex
)
P551
Drive profile
0
Off
Identifier:
CAN ID for Rx-PDO1: 200
hex
+ NODE-ID
à 200
hex
+ 32
hex
= 232
hex
(control word + setpoint 1)
CAN ID for Tx-PDO1: 180
hex
+ NODE-ID
à 180
hex
+ 32
hex
= 1B2
hex
(status word + actual value 1)