7 Examples

BU 0060 GB-4112

95

7. Examples

Various examples are shown below to clarify the control and parameterisation of the frequency
inverter with the bus system.

Pos : 177 /Anleit ungen/El ektr oni k/Buss yst eme/ 7. Beis piel- T elegramme/N etz einschalt en [C ANopen BU 0060] @ 1\ mod_1342785004232_388. doc x @ 35839 @ 25 @ 1

7.1 Mains switch-on

After the CAN participant has been switched on it logs into the system with the CAN ID: 700

hex

+ Node

ID.

Example

Node ID: 50

dec

à 32

hex

Mains On

à if the participant was recognised 732

hex

is transmitted.

As no valid telegram was sent at this time, the inverter switches to the status "Starting disabled" (

à

status word: 0B40).

Pos : 178 /Anleit ungen/El ektr oni k/Buss yst eme/ 7. Beis piel- T elegramme/ Operational setzen der Bus Teilnehmer [CAN open BU0060] @ 1\ mod_1342786735533_388.doc x @ 35863 @ 2 @ 1

7.2 Operational settting of the bus participant

Be sending 0001 to ID000 all participants are set to "Operational".

Pos : 179 /Anleit ungen/El ektr oni k/Buss yst eme/ 7. Beis piel- T elegramme/ Proz ess daten ( PDO) [CAN open BU0060] @ 1\mod_1342776486166_388.doc x @ 35815 @ 2555 @ 1

7.3 Process data (PDO)

The exchange of process data is carried out via PDOs and is illustrated in the following example.

Example:

Communication via:

Technology unit SK TU4-CAO

Scope of data:

STW and SW1

Communication settings on the frequency inverter

Parameter number

Parameter name

Setting

Meaning

P509

Setpoint source

6 or 17

CANopen

P510

Setpoint source

0

Auto

P515 (or rotary
coding switch on
the bus module)

CAN address
(Node ID)

50

(50

dec

= 32

hex

)

P551

Drive profile

0

Off

Identifier:

CAN ID for Rx-PDO1: 200

hex

+ NODE-ID

à 200

hex

+ 32

hex

= 232

hex

(control word + setpoint 1)

CAN ID for Tx-PDO1: 180

hex

+ NODE-ID

à 180

hex

+ 32

hex

= 1B2

hex

(status word + actual value 1)