5 parameters, P509 interface, P510 bus interface auxiliary setpoint – NORD Drivesystems BU0060 User Manual

Page 71

Advertising
background image

5 Parameters

BU 0060 GB-4112

71

P509

Interface

(Interface)

0 ... 21

{ 0 }

Selection of the interface via which the FI is controlled.

0 = Control terminals or keyboard control ** with the ControlBox (if P510=0), the

ParameterBox (not ext. P-box) or via BUS I/O Bits.

1 = Only control terminals , the FI can only be controlled via the digital and analog

inputs or via the bus I/O Bits.

5 = CAN setpoint*, the frequency setpoint is transferred via CAN. Control via the digital

inputs is still active.

6 = CAN control word*, the control signals (enable, direction of rotation, ...) are

transferred via UCAN, the setpoint via the analog input or the fixed frequencies.

7 =

CAN*, all control data is transferred via CAN. The analog input and the digital inputs
have no function (except safety functions)

11 = CAN Broadcast*, the inverter receives all of the control data via CAN without

responding to the master (e.g. for the synchronisation function). The analog input and
the digital inputs have no function (except safety functions)

15 = CANopen setpoint*, as for setting 5, but CANopen

16 = CANopen control word*, as for setting 6, but CANopen

17 = CANopen*, as for setting 7, but CANopen

*) Keyboard control (ControlBox, ParameterBox) is blocked, parameterisation is still possible.

**) If the communication during keyboard control is interrupted (time out 0.5 sec),

the FI will block without an error message.

Pos : 118 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P510 – Sc hni ttst elle Bus nebens oll wert e [SK 700E] @ 1\ mod_1335780555886_388. doc x @ 24850 @ @ 1

P510

Bus interface auxiliary setpoint

(Bus interface auxiliary setpoints)

SK 700E/

SK750E

S

0 ... 8

{ all 0 }

Selection of the interface via which the FI is controlled.

0 = Auto (=P509): The source of the auxiliary setpoint is automatically derived from the

setting in the parameter P509 >Interface<

1 = USS

2 = CANbus

3 = Profibus

4 = InterBus

5 = CANopen

6 = DeviceNet

7 = Reserved

8 = CAN Broadcast

Pos : 119 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P513 – Tel egrammausf allzei t @ 0\ mod_1328092407709_388.doc x @ 11180 @ @ 1

Advertising