2.1.4 CANopen module, SK TU3-CAO

This CANopen module can be
used for all SK 500E devices. It
occupies the technology slot
which can then no longer be used
for control and display modules.
Alternatively, the SimpleBox SK
CSX-0 can be plugged in to the
CANopen module and connected
to the frequency inverter via the
RS232/485 interface.

The CANopen module must be
provided with a 24 V external
power supply
(via SUB – D9
connection). This CAN participant
can therefore be identified by the
master system even without a
voltage supply to the frequency
inverter. The data required for this
purpose are set using a rotary
coding switch. This Bus data is
read in when the 24V is applied
from the frequency inverter.

1

CANopen Status LEDs

CR

(green)

CANopen RUN

CE

(red)

CANopen ERROR

DR

(green)

Module status

GB

(red)

Module error

2

Termination resistor



(ON)

Connected



(OFF)

Not connected

3

Shielding terminal

Connection to PE of the
frequency inverter to suppress
interference in the Bus lines

4

SUB – D9

GND

CAN_L

6

1

5

9

GND

CAN_H

24V in

Baud rate (BAUD)

Transfer rates of up to 500 kbit/s can be used (optionally up to 1Mbit/s).

If BAUD is set to PGM the value from parameter P514 is used as the baud rate.

Supply voltage

The supply voltage is 24 V DC ±25% (Pin 9 = 24 V, Pin 3 = GND, approx. 80 mA). The connection is
made via the SUB-D9 connector.

Termination resistor

The termination resistor for the last Bus participant is located on the CANopen Bus module.

CAN address, setting the ID (IDx1 and ID10)

The rotary switches IDx1 and IDx10 can be used to set the node identifier in decimal code in the
range from 01...99

dez

.

Example: Node ID = 64

à

IDx10 = 6, IDx1 = 4

If BAUD is set to PGM the value from parameter P515 of the frequency inverter is used as the node
identifier.

Information

Rotary coding switches

The settings made using the rotary coding switch are not transferred to the frequency inverter or saved. Changed
settings are only adopted when the 24V supply is applied ("Power ON").