4 Communication and Protocol

BU 0060 GB-4112

51

Figure 9: Sequence of data transfer

Pos : 80 /Anl eitungen/ Elektroni k/ Bus s yst eme/4. Kommuni kati on und Prot okoll + Proz ess datentr ans fer /CAN open [ BU 0060]/D as C ANnord Pr ot okoll /Broadc ast- T elegramme [CAN] @ 1\ mod_1342083279128_388. doc x @ 31952 @ 3 @ 1

4.2.5 Broadcast telegrams

To control several frequency inverters simultaneously (e.g. same enable and same setpoint), it is
possible to address frequency inverter groups or all frequency inverters using broadcast telegrams.
This means that, in addition to the identifiers described above, additional broadcast identifiers for each
frequency inverter are also valid. A range of 32 addresses is assigned to one broadcast identifier. All
connected frequency inverters can be controlled using the broadcast identifier 1032.

CAN address (P515)

Broadcast identifier

00 - 31

1024 (400h)

32 - 63

1025 (401h)

64 - 95

1026 (402h)

96 - 127

1027 (403h)

128 - 159

1028 (404h)

160 - 191

1029 (405h)

192 - 223

1030 (406h)

224 - 255

1031 (407h)

0 - 255

1032 (408h)

Table 12: Assignment of CAN address (P515) to the broadcast identifier

Actual value
from FI

Setpoint
from Master

Timing process data

t

PZD

Parameter
order from Master

Parameter
response
from FI

t

PKW

Timing parameter data