CANopen – Supplementary manual options for NORD - Frequency Inverters

52

BU 0060 GB-4112

The broadcast function is activated when the interface parameter (P509=11) is set to CAN broadcast.

This assumes that the control data and setpoint are specified via CANnord.

Only process data can be transferred with broadcast telegrams. Status data are not returned
(unconfirmed service).

Pos : 81 /Anl eitungen/ Elektroni k/ Bus s yst eme/4. Kommuni kati on und Prot okoll + Proz ess datentr ans fer /CAN open [ BU 0060]/D as C ANnord Pr ot okoll /Parametrier ung i m M ode CAN [CAN ] @ 2\ mod_1347285948586_388.doc x @ 44341 @ 3 @ 1

4.2.6 Parametrerisation in CAN mode

In order to process a parameter (read or write / change an inverter parameter) a unique order
telegram is sent to the frequency inverter from the master. The FI responds with the corresponding
response.

In principle, the area of the telegram which is relevant for processing the parameter consists of a
parameter identification, in which the type of order (Write, Read etc.) and the relevant parameters
are specified. Individual parameter sets or array elements can be addressed with the aid of the Index.
The parameter value contains the value to be written or read.

Pos : 82 /Anl eitungen/ Elektroni k/ Bus s yst eme/4. Kommuni kati on und Prot okoll + Proz ess datentr ans fer /CAN open [ BU 0060]/D as C ANnord Pr ot okoll /Paramet er kennung (PKE) [CAN] @ 2\mod_1347286233845_388. doc x @ 44366 @ 5555 @ 1

Parameter label (PKE)

The order or response and the associated parameters are encrypted in the parameter label (PKE).

1

2

3

4

PKE

IND

PWE1

PWE2

15

14

13

12 11

10 9

8

7

6

5

4

3

2

1

0

AK

SPM

PNU

The parameter label (PKE) is always a 16 bit value.

PNU

Bits 0 to 10 contain the number of the required parameter (PNU), or the number of the
current parameter in the response telegram of the frequency inverter.

Information

Parameter number PNU

For the inverter parameter numbers (PNU) of the particular inverter series please refer to the relevant operating
instructions.

SPM

Bit 11 is the toggle-bit for spontaneous messages. This function is not supported!

AK

Bits 12 to 15 contain the order or response label.

Information

Labelling: AK

Both the order label and the response label are abbreviated as AK. Therefore, care must be taken when reading
or interpreting the order processing description in this section.