5.2 SK 5xxE BUS Parameters

Information

Number of bus setpoints and actual values

The SK 54xE frequency inverter can administer 5 setpoint or actual values (each 16 bit). However, via the
technology unit SK TU3-... the bus system only provides the possibility of processing setpoint or actual values 1 ...
3.

Pos : 138 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ P4xx St euer klemmen @ 0\ mod_1327678262854_388. doc x @ 9027 @ 5 @ 1

5.2.1 Control terminals

Parameter
{factory setting}

Setting value / Description / Note

Supervisor

Parameter
set

Pos : 139 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P480 – Funkti on Bus I/O I n Bits [SK 5xxE] @ 0\ mod_1328002641156_388.doc x @ 10779 @ @ 1

P480

[-01]

...

[-12]

Function BusIO In Bits

(Bus I/O In Bits function)

S

0 ... 80

{ all 0 }

The Bus I/O In Bits are perceived as digital inputs (P420). They can be set to the same functions.

In order to use this function, one of the bus setpoints (P546) must be set to >Bus I/O In Bits 0-7
<. The required function must then be assigned to the relevant bit.

With the SK 54xE in association with IO extension modules these I/O bits can also process their
input signals.

[-01] = Bus I/O In Bit 0 (or SK54xE and above: + DI1 of the second IOE)

[-02] = Bus I/O In Bit 1 (or SK54xE and above: + DI2 of the second IOE)

[-03] = Bus I/O In Bit 2 (or SK54xE and above: + DI3 of the second IOE)

[-04] = Bus I/O In Bit 3 (or SK54xE and above: + DI4 of the second IOE)

[-05] = Bus I/O In Bit 4 (or SK54xE and above: + DI1 of the first IOE)

[-06] = Bus I/O In Bit 5 (or SK54xE and above: + DI2 of the first IOE)

[-07] = Bus I/O In Bit 6 (or SK54xE and above: + DI3 of the first IOE)

[-08] = Bus I/O In Bit 7 (or SK54xE and above: + DI4 of the first IOE)

[-09] = Flag 1

[-10] = Flag 2

[-11] = Bit 8 BUS control word

[-12] = Bit 9 BUS control word

The possible functions for the Bus In Bits can be found in the table of functions for the digital
inputs. Function {14} "Remote control" is not possible.