2 led display with the technology unit, Cannord led display, Led display canopen – NORD Drivesystems BU0060 User Manual

Page 92: Led display with the technology unit, Table 29: led display, canopen module status

Advertising
background image

CANopen – Supplementary manual options for NORD - Frequency Inverters

92

BU 0060 GB-4112

6.1.2 LED display with the technology unit:

The status of the technology unit is indicated by the integrated LEDs:

CANnord LED display

LED

Meaning

TxD (green)

Transmitting CAN data

RxD (green)

Receiving CAN data

Table 27: LED display, CANnord communication status

LED display CANopen

LED

Display

Meaning

CR (green)

Single flashing (1s)

CANopen status STOPPED

Flashing (0.5s)

CANopen status PRE-OPERATIONAL

Flashing (0.25s)

No other subscriber is in the bus or the wiring is faulty. (only possible
when flashing with CE)

To:

CANopen status OPERATIONAL

CE (red)

Off

No error

Flashing

Bus warning, CAN controller error counter has reached or exceeded
the warning limit.

Check wiring / shielding / termination resistors

No other subscribers available

To:

Bus off, CAN controller has disconnected from the bus because a
serious error has occurred, e.g.:

Wiring error
Incorrect baud rate set

Table 28: LED display, CANopen communication status

LED

Display

Meaning

DR (green)

Off

No voltage supply

Flashing

Initialisation (init. phase)

On

Module OK

DE (red)

Off

No error

Flashing (0.2s)

Initialisation phase

Flashing (0.5s)

Timeout error

Single flashing (1s)

Inverter error (see frequency inverter instructions)

To:

System error, e.g. plug contact not correct

Table 29: LED display, CANopen module status