P545 actual bus value 3, P546 digital bus setpoint 1, P546 – NORD Drivesystems BU0060 User Manual

Page 84: Digital bus setpoint

Advertising
background image

CANopen – Supplementary manual options for NORD - Frequency Inverters

84

BU 0060 GB-4112

P545

Actual bus value 3

(Actual bus value 3)

S

P

0 ... 24

{ 0 }

This parameter is identical to P543.

Condition is PPO 2 or PPO 4 type (P507).

Pos : 155 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P546 – Funkti on Bus-Soll wert 1 [ SK 500... 535E] @ 0\ mod_1328097962990_388. doc x @ 11916 @ @ 1

P546

Digital Bus setpoint 1

(Function of bus setpoint 1)

S

P

0 ... 55

{ 1 }

In this parameter, a function is allocated to the output setpoint 1 during bus actuation.

The possible analog functions can be found in the following table.

NOTE:

For further details please refer to the manual for the frequency inverter (P400, P546),

the relevant BUS operating instructions or the manuals BU 0510 / BU0550.

Pos : 156 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P546 – Funkti on Bus-Soll wert e [SK 54xE] @ 0\mod_1328098077630_388. doc x @ 11939 @ @ 1

P546

[-01]

...

[-05]

Digital Bus setpoint

(Function of bus setpoint)

S

P

0 ... 57

{ [-01] = 1 }

all other { 0 }

In this parameter, during bus actuation a function is allocated to the setpoint provided.

NOTE:

The setpoints 4 and 5 must be supported by the relevant bus module. For further
details please refer to the manual for the frequency inverter (P400, P546), the
relevant BUS operating instructions or the manuals BU 0510 / BU0550.

[-01] = Bus setpoint 1

[-02] = Bus setpoint 2

[-03] = Bus setpoint 3

[-04] = Bus setpoint 4

[-05] = Bus setpoint 5

0 =

Off

16 = Process controller lead

1 =

Setpoint frequency

17 = BusIO In Bits 0...7

2 =

Torque current limit (P112)

18 = Curve travel calculator

3 =

Actual frequency PID

19 = Set relays, "Output status"

(P434/441/450/455=38)

4 =

Frequency addition

20 = Set analog output (P418=31)

5 =

Frequency subtraction

21 = ... 45 reserved from SK 530E and above

à

BU 0510

6 =

Current limit (P536)

46 = Setpoint Torque processreg., "Setpoint

torque process controller"

7 =

Maximum frequency (P105)

47 = reserved from SK 530E and above

à

BU 0510

8 =

Actual PID frequency limited

48 = Motor temperature (SK 540E and above)

9 =

Actual PID frequency monitored

49 = reserved from SK 540E and above

à

BU 0510

10 = Torque servo mode (P300)

53 = d-correction F process (SK 540E and

above)

11 = Torque precontrol (P214)

54 = d-correction Torque (SK 540E and above)

12 = Reserved

55 = d-correction F+torque (SK 540E and

above)

13 = Multiplication

56 = reserved from SK 540E and above

à

BU 0510

14 = Process controller actual value

57 = reserved from SK 540E and above

à

BU 0510

15 = Process controller setpoint