2.3.2 CANopen module, SK TU2-CAO

The CANopen module must be
provided with a 24 V external
power supply
(via SUB - D9
connection). This CAN
participant can therefore be
identified by the master system
even without a voltage supply to
the frequency inverter. The data
required for this purpose are set
using a rotary coding switch.
This Bus data is read in when
the 24 V is applied from the
frequency inverter.

1

CANopen Status LEDs

CR

(green)

CANopen RUN

CE

(red)

CANopen ERROR

DR

(green)

Module status

GB

(red)

Module error

2

SK 300E status LEDs

On

(green)

Mains voltage applied

Error

(red)

Inverter error*

* The flashing frequency corresponds to
the error number (see BU0300)

3

Rotary coding switches

ID-H

Addressing ( ID x 10 )

ID-L

Addressing ( ID x 1 )

Baud

Baud rate

4

M12 BUS-In / BUS-Out

4

Plug connector

assignment:

1

PE (shield) *

2

+24V

3

GND

4

CAN-H

5

CAN-L

* Pin 1 and housing

Baud rate (BAUD)

Transfer rates of up to 500 kbit/s can be used (optionally up to 1Mbit/s).

If BAUD is set to PGM the value from parameter P514 is used as the baud rate.

Supply voltage

The supply voltage is 24 V DC ±25% (Pin 9 = 24 V, Pin 3 = GND, approx. 80 mA). The connection is
made via the SUB-D9 connector.

Termination resistor

The termination resistor for the last bus participant can be switched to the output (BUS-Out) of the
final frequency inverter as the termination connector.

CAN address, setting the ID (ID-L and ID-H)

The rotary switches ID-L and ID-H can be used to set the node identifier in decimal code in the range
from 01...99

dez

.

Example: Node ID = 64

à

ID-H = 6, ID-L = 4

If BAUD is set to PGM the value from parameter P515 of the frequency inverter is used as the node
identifier.

Information

Rotary coding switches

The settings made using the rotary coding switch are not transferred to the frequency inverter or saved. Changed
settings are only adopted when the 24V supply is applied ("Power ON").