Appendix 3: Digital current loop module

105

Single loop wiring

•

Set the address of the transmitter; you can choose any number
between 1 and 99. In this example the address is 22:

>addr 22
Address : 22

•

Set the serial bus settings according to your network specifications.
This setting will become valid after next RESET or power off:

>seri 2400 e 7 1 h
2400 E 7 1 HDX

•

Set the transmitter in POLL mode:

>smode poll
Serial mode : POLL

NOTE 1

The SMODE command must be given last.

NOTE 2

The transmitter outputs no prompt (>) after the SMODE
POLL command and it only reacts to commands which
include its address.

•

Check that the transmitter responds to its address:

send 22
RH= 24.4 %RH T= 29.1 'C

•

Disconnect the terminal.

•

Remount the digital current loop module.

•

Close the cover.

•

When all transmitters on the network have been configured, switch
them off.

Dual loop operation

Single pair/dual pair use is configured through wiring (see figure on page 2).

The following procedure must be repeated with all transmitters.

•

Open the transmitter cover.

•

Pull out the digital current loop module, if it is already mounted.