13

3.3

Grounding

A single electrical cable with a screen and three to ten wires is recommended
for power and analogue output/serial bus connections. The cable diameter
should be 7...10 mm.

The screen of the electrical cable must be grounded properly to achieve best
possible EMC performance. Recommended cable shield is done in the cable
gland as shown below.

remove the brass disks, rubber ring and nut from the transmitter
housing

strip 165 mm of the cable insulation, but leave 25 mm of the braid
visible

slip the nut and rubber ring over the cable insulation

slip the brass disk that has the bigger hole in it over the braid so that
it rests against the cable insulation

slip the other brass disk over the wires to the middle of the braid

(If the cable diameter is less
than 7mm, use a shrinking
tube or an adhesive tape)

cable

braid

flexible wires 0.5 mm
(AWG 20), stranded wires
recommended

2

D = Ø 7...10 mm

3

brass
disks

25

rubber
ring

nut

brass disks

140

165

shielding tube

braid

push back the braid and press it between the two brass disks to
achieve a full 360° grounding; the fold between the disks should have
the same diameter as the brass disks

secure the braid with a shielding tube

insert the wires into the transmitter housing through the gland