Hmp243 transmitter, Hmp243 transmitter controller – Vaisala HMP240 User Manual

Page 18

Advertising
background image

HMP240
User's Guide

M210300en

16

3.4.1

Connection to a 24 VAC supply

The HMP240 transmitter can also be connected to a 24 VAC supply without
an external rectifier. However, when more than one transmitter is connected to
one 24 VAC transformer, a common loop is formed and there is an increased
risk of a short-circuit. To avoid this, always use separate floating supply for
each transmitter (see Figure 3.7 A). However, if several transmitters have to
share one transformer, the phase (

) must always be connected to + connector

in each transmitter (see Figure Figure 3.7 B).

24 VAC

HMP243 transmitter

HMP243 transmitter

Controller