Boom sensor calibration position 2 -72 – JLG 1350SJP Service Manual User Manual

Page 448

Advertising
background image

SECTION 6 - JLG CONTROL SYSTEM

6-72

– JLG Lift –

3121142

23.

After making sure the machine is in Calibration Position
1, hit Enter. The screen will read:

24.

Lift up to stop (full stroke of cylinder) for Calibration
Position 2. When the machine is in that position, hit
Enter.

The screen will read:

Figure 6-15. Boom Sensor Calibration Position 2