Boom sensor calibration position 6 -76, Boom sensor calibration position 7 -76 – JLG 1350SJP Service Manual User Manual
Page 452
Advertising
SECTION 6 - JLG CONTROL SYSTEM
6-76
– JLG Lift –
3121142
28.
Retract to stop (boom must be fully retracted) for Cali-
bration Position 6.
When the machine is in the proper position, hit Enter.
The screen will read:
29.
Lift down to stop (boom must be on boom rest) for Cali-
bration Position 7.
When the machine is in the proper position, hit Enter.
The screen will read as follows:
Figure 6-19. Boom Sensor Calibration Position 6
Figure 6-20. Boom Sensor Calibration Position 7