SECTION 6 - JLG CONTROL SYSTEM

3121142

– JLG Lift –

6-129

Table 6-11. Load Moment Pin Troubleshooting: Moment Pin Horizontal Force Out of Range

STEP

FAULT CODE/SYMPTOM

REPAIR

YES

NO

1

8/6 MOMENT PIN HORIZONTAL FORCE OUT OF RANGE The
horizontal force is out of allowed range.

Check to see if the platform is over-
loaded in the vertical position. Check
the rated capacity requirement.

Remove excess weight

Go to step 2

2

Check to see if any additional accesso-
ries have been added to the platform
without proper calibration.

Perform the Boom Sen-
sor calibration process.

Go to step 3

3

Perform the BCS daily check procedure
to make sure the boom sections are
stopping correctly at the witness marks
matching their capacity selection.

Go to step 4

Perform the Boom Sensor cali-
bration process.

4

Inspect the job the machine is perform-
ing, making sure that there is no addi-
tional force applied when the boom
sections are in the horizontal position.
Also consider weather conditions
(Wind).

Go to step 5

Position machine correctly.

5

Use the Analyzer, scroll to the DIAGNOS-
TICS menu, press ENTER, then scroll to
the MOMENT menu, and press ENTER,
check to see if Actual / Over / Under
moment values are registering on the
screen display.

Go to step 6

Replace the load moment pin. &
Perform the Boom Sensor cali-
bration process.

6

If they are, refer to Figure 6-32.,
Moment Chart f
or comparable values, if
the values are not close, try boom sen-
sor calibration to see if the values come
within the chart.

If the problem still exists, verify
steps 1-6 again before contact-
ing the JLG Service Dept.

Replace the load moment pin. &
Perform the Boom Sensor cali-
bration process.