5.2.7

External voltage supply

The communication module can be externally supplied with voltage via separate supply cables at

the 2-pin plug connector X250.

The external voltage supply of the communication module is necessary if the power supply for the

basic device fails but communication via the fieldbus is to be maintained.
Access to parameters of a standard device disconnected from the mains is not possible.

Assignment of the X250 plug connector

Data of the terminals

Note!

With external voltage supply, always use a separate power supply unit, safely separated

to EN 61800-5-1 in every control cabinet (SELV/PELV).

Name

Explanation

+

U = 24 V DC (20.4 ... 28.8 V)

I = 140 mA

-

Reference potential for external voltage supply

Range

Values

Electrical connection

2-pole connector with screw connection

Possible connections

Rigid:

1.5 mm

2

(AWG 16)

Flexible:

Without wire end ferrule

1.5 mm

2

(AWG 16)

With wire end ferrule, without plastic sleeve

1.5 mm

2

(AWG 16)

With wire end ferrule, with plastic sleeve

1.5 mm

2

(AWG 16)

Starting torque

0.5 ... 0.6 Nm (4.4 ... 5.3 lb-in)

Stripping length

6 mm