9error messages – Lenze E94AYCEC User Manual

Page 62

Advertising
background image

9

Error messages

9.2

POWERLINK error messages

62

Lenze · E94AYCEC Communication module (POWERLINK CN) · Communication Manual · DMS 3.0 EN · 08/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

0x18266 98918

EL_EPL_COM_CRC

Faulty Ethernet frames (CRC error) have been detected.

Causes & remedy:

• see error description

EPL: Defective telegram (CRC) detected [0x00c88266] ( 59)

Codes:

C13131/3

/

C14131/3

(monitoring threshold)

C13891/4

/

C14891/4

(error response)

C13131/1

/

C14131/1

(error counter)

0x38266 229990

QL_EPL_COM_CRC

0x48266 295526

WL_EPL_COM_CRC

0x68266 426598

I__EPL_COM_CRC

0x18267 98919

EL_EPL_MN_LOSS_

CN

The MXI connection to the Servo Drive 9400 is interrupted or a node

has failed.

Causes & remedy:

• see error description

EPL: Lost connection to 9400 [0x00c83100] ( 56)

EPL: Failure of a network node [0x00c88267] ( 59)

Codes:

C13891/5

/

C14891/5

(error response)

C13132

/

C14132

(CN: link interruptions)

0x38267 229991

QL_EPL_MN_LOSS_

CN

0x48267 295527

WL_EPL_MN_LOSS_

CN

0x68267 426599

I__EPL_MN_LOSS_

CN

0x18283 98947

EL_EPL_ADDRESS_

MN

An invalid IP address has been assigned by the Managing Node via

POWERLINK or set as Node ID.

OR:

The address setting of the managing node (Node ID = ’240’) has been

assigned several times.

Causes & remedy:

• see error description

EPL: Invalid address selected [0x00c88261] ( 58)

EPL: MN address assigned double [0x00c88283] ( 60)

Codes:

• see

Node address setting ( 35)

• see

Settings and displays in the »Engineer« ( 37)

0x38283 230019

QL_EPL_ADDRESS_

MN

0x48283 295555

WL_EPL_ADDRESS_

MN

0x68283 426627

I__EPL_ADDRESS_

MN

Error number

Name

Description

hex

dec