Lenze · E94AYCEC Communication module (POWERLINK CN) · Communication Manual · DMS 3.0 EN · 08/2014 · TD17

67

10

Parameter reference

10.2

Parameters of the communication module for slot MXI1

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C13028

Description of the bits 0 ... 31

*) Not permissible for 9400 Servo Drives.

Parameter | Name:

C13028 | EPL node declaration CN

Data type: UNSIGNED_32

Index: 11547 = 0x2D1B

EPL index: See subcodes

The code describes the controlled nodes 1 ... 100 and their properties.
Value is bit-coded:

Bit 0 ... 31 see below

Subcodes

Lenze setting

Info

EPL index

C13028/1

0

EPL node declaration CN

0x1F81.0x01

...

...

...

...

C13028/100

0

EPL node declaration CN

0x1F81.0x64

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Bit

Relevance

Lenze

Value

Description

MN

CN

0 (LSB)

0, 1

0

EPL node with this ID does not exist.

1

EPL node with this ID exists.

1

0, 1

0

EPL node with this ID is not a controlled node.

1

EPL node with this ID is a controlled node.

2

1

0

*)

On detection of a booting controlled node, the application will not be informed.

1

On detection of a booting controlled node, the application will be informed and the controlled node

will be started.

3

1

0

Optional controlled node

1

Obligatory controlled node

4

0

0

The managing node is allowed to send reset commands.

1

*)

The managing node must not send any reset command.

5

0

0

Software version verification of the controlled node is not required.

1

*)

Software version verification of the controlled node is required.

6

0, 1

0

Automatic application software update is not allowed.

1

Automatic application software update is allowed.

7

-

-

0

0

Reserved / No function

8

0, 1

0

Isochronously accessed controlled node

1

Asynchronously accessed controlled node (bit 9 is irrelevant)

9

0

0

Continuously accessed controlled node

1

Multiplex EPL nodes are supported.

10

0

0

No "POWERLINK to standard Ethernet" router function.

1

The device can be used as an "POWERLINK to standard Ethernet" router (router type 1).

11

0

0

No "POWERLINK to fieldbus" router function.

1

The device can be used as an "POWERLINK to fieldbus" router (router type 1).

12

0

0

The managing node does not send any PRes frames

1

The managing node sends PRes frames

13 ... 30

-

-

0

0

Reserved / No function

31

(MSB)

0, 1

0

Bits 0 ... 30 inhibited

1

Bits 0 ... 30 enabled