C13045 | epl host name, C13060 | epl cycle time, C13045 – Lenze E94AYCEC User Manual

Page 72: C13060, 10 parameter reference

Advertising
background image

10

Parameter reference

10.2

Parameters of the communication module for slot MXI1

72

Lenze · E94AYCEC Communication module (POWERLINK CN) · Communication Manual · DMS 3.0 EN · 08/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C13045

C13060

Parameter | Name:

C13045 | EPL host name

Data type: VISIBLE_STRING

Index: 11530 = 0x2D0A

EPL index: 0x1F9A

The code defines a DNS-compatible device name. The length is limited to 15 characters.

The device name must be unambiguous within the network domain.

Naming convention:

The device name

• starts with a character

• ends with a character or digit

The device name consists of

• letters ([A ... Z], [a ... z])

• digits ([0 ... 9])

• hyphen ([ - ])

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13060 | EPL cycle time

Data type: UNSIGNED_32

Index: 11515 = 0x2CFB

EPL index: 0x1006

The code declares the length of the EPL cycle in s.

• In the configured state, this code must have an identical value in all EPL nodes.

• The selected value must correspond to the actual bus cycle time so that the internal monitoring functions work

correctly.

Selection list

(Lenze setting printed in bold)

500 0.5

1000 1
2000 2
3000 3
4000 4
5000 5
6000 6
7000 7
8000 8
9000 9

10000 10
11000 11
12000 12
13000 13
14000 14
15000 15
16000 16
17000 17
18000 18
19000 19
20000 20

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT