C13041 | epl version, C13042 | current epl device address, C13043 | epl device address selection – Lenze E94AYCEC User Manual

Page 71: C13044 | epl device address sw, C13044, C13042, 10 parameter reference

Advertising
background image

Lenze · E94AYCEC Communication module (POWERLINK CN) · Communication Manual · DMS 3.0 EN · 08/2014 · TD17

71

10

Parameter reference

10.2

Parameters of the communication module for slot MXI1

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C13041

C13042

C13043

C13044

Parameter | Name:

C13041 | EPL version

Data type: UNSIGNED_8

Index: 11534 = 0x2D0E

EPL index: not available

The code describes the version of the POWERLINK communication profile implemented by the communication

module.

The higher-order nibble describes the major version, the lower order nibble describes the minor version. The

implemented value corresponds to the POWERLINK version 2.0.

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13042 | Current EPL device address

Data type: UNSIGNED_8

Index: 11533 = 0x2D0D

EPL index: 0x1F93.0x01

The code displays the currently valid EPL node address (Node ID).

• The node ID must be unequivocal in the EPL network segment.

• See also

C13044

.

Display area

(min. value | unit | max. value)

1

240

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13043 | EPL device address selection

Data type: UNSIGNED_8

Index: 11532 = 0x2D0C

EPL index: 0x1F93.0x02

The code indicates whether the EPL node address (node ID) has been set via DIP switches at the communication

module or via the software.

• 0: Node ID has been set via software (

C13044

).

• 1: Node ID has been set via DIP switches at the communication module.

Node address setting ( 35)

Display area

(min. value | unit | max. value)

0

1

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13044 | EPL device address SW

Data type: UNSIGNED_8

Index: 11531 = 0x2D0B

EPL index: 0x1F93.0x03

This code serves to set the EPL node address (node ID) via the software.

The value "0" (Lenze setting) is not a valid node ID. It serves to activate the setting via the DIP switches.

Node address setting ( 35)

Setting range

(min. value | unit | max. value)

Lenze setting

1

240 0

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Advertising