C13126

C13127

C13131

Parameter | Name:

C13126 | EPL CN: Frame collisions

Data type: UNSIGNED_32

Index: 11449 = 0x2CB9

EPL index: See subcodes

The code indicates the number of POWERLINK collisions detected by the controlled node.

Each event is counted. Every single event is followed by an error message. No threshold value management is

implemented.
Setting range

(min. value | unit | max. value)

0

4294967295

Subcodes

Lenze setting

Info

EPL index

C13126/1

0

CumulativeCnt_U32

0x1C0A.0x01

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13127 | EPL CN: Sync loss

Data type: UNSIGNED_32

Index: 11448 = 0x2CB8

EPL index: See subcodes

The controlled node expects SoC frames in time intervals which correspond to the cycle time (

C13060

).

The code indicates the error counters for missing SoC frames.

The monitoring response is determined via

C13891/3

.

Setting range

(min. value | unit | max. value)

0

4294967295

Subcodes

Lenze setting

Info

EPL index

C13127/1

0

CumulativeCnt_U32

0x1C0B.0x01

C13127/2

0

ThresholdCnt_U32

0x1C0B.0x02

C13127/3

9

Threshold_U32

0x1C0B.0x03

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13131 | EPL CN: Frame error (CRC)

Data type: UNSIGNED_32

Index: 11444 = 0x2CB4

EPL index: See subcodes

The code indicates the number of frame checksum errors detected by the controlled nodes.

The monitoring response is determined via

C13891/4

.

Setting range

(min. value | unit | max. value)

0

4294967295

Subcodes

Lenze setting

Info

EPL index

C13131/1

0

CumulativeCnt_U32

0x1C0F.0x01

C13131/2

0

ThresholdCnt_U32

0x1C0F.0x02

C13131/3

9

Threshold_U32

0x1C0F.0x03

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT