Error messages

9.1

Error messages of the communication module

58

Lenze · E94AYCEC Communication module (POWERLINK CN) · Communication Manual · DMS 3.0 EN · 08/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

EPL: Fieldbus watchdog activated [0x00c88130]

EPL: DataExchange exited [0x00c88131]

EPL: Invalid address selected [0x00c88261]

EPL MN: Network has not been started (bootup-1) [0x00c88263]

EPL MN: Not all nodes are in the operational status (bootup-2) [0x00c88264]

Response (Lenze setting printed in bold)

Setting: not possible

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  warning  Information

Cause

Remedy

Communication module is defective.

Send communication module together with a

description of the fault to Lenze.

Response (Lenze setting printed in bold)

Setting:

C13883

/

C14883

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The POWERLINK data exchange has been terminated.

• Check wiring.

• Plug network cable into POWERLINK terminal X251 or

X252.

Response (Lenze setting printed in bold)

Setting: not possible

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

An invalid IP address has been assigned by the managing

node via POWERLINK or set as node ID.

• Ensure that a valid IP address is assigned by the

managing node via POWERLINK.

• Set valid node ID.

Node address setting ( 35)

Response (Lenze setting printed in bold)

Setting:

C13891/2

/

C14891/2

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

• The Managing Node could not start the POWERLINK

network.

• Not all required nodes were found.

• Check if all nodes are switched on

• Check address setting and wiring.

Response (Lenze setting printed in bold)

Setting:

C13891/2

/

C14891/2

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The Managing Node could not transfer all nodes into the

"NMT_CS_OPERATIONAL" status via process data

exchange.

Check whether single nodes are in error status.