Parameter reference

10.3

Parameters of the communication module for slot MXI2

98

Lenze · E94AYCEC Communication module (POWERLINK CN) · Communication Manual · DMS 3.0 EN · 08/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C14126

C14127

C14131

Parameter | Name:

C14126 | EPL CN: Frame collisions

Data type: UNSIGNED_32

Index: 10449 = 0x28D1

EPL index: See subcodes

The code indicates the number of POWERLINK collisions detected by the controlled node.

Each event is counted. Every single event is followed by an error message. No threshold value management is

implemented.
Setting range

(min. value | unit | max. value)

0

4294967295

Subcodes

Lenze setting

Info

EPL index

C14126/1

0

CumulativeCnt_U32

0x1C0A.0x01

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C14127 | EPL CN: Sync loss

Data type: UNSIGNED_32

Index: 10448 = 0x28D0

EPL index: See subcodes

The controlled node expects SoC frames in time intervals which correspond to the cycle time (

C14060

).

The code indicates the error counters for missing SoC frames.

The monitoring response is determined via

C14891/3

.

Setting range

(min. value | unit | max. value)

0

4294967295

Subcodes

Lenze setting

Info

EPL index

C14127/1

0

CumulativeCnt_U32

0x1C0B.0x01

C14127/2

0

ThresholdCnt_U32

0x1C0B.0x02

C14127/3

9

Threshold_U32

0x1C0B.0x03

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C14131 | EPL CN: Frame error (CRC)

Data type: UNSIGNED_32

Index: 10444 = 0x28CC

EPL index: See subcodes

The code indicates the number of frame checksum errors detected by the controlled nodes.

The monitoring response is determined via

C14891/4

.

Setting range

(min. value | unit | max. value)

0

4294967295

Subcodes

Lenze setting

Info

EPL index

C14131/1

0

CumulativeCnt_U32

0x1C0F.0x01

C14131/2

0

ThresholdCnt_U32

0x1C0F.0x02

C14131/3

9

Threshold_U32

0x1C0F.0x03

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT