Lenze · E94AYCEC Communication module (POWERLINK CN) · Communication Manual · DMS 3.0 EN · 08/2014 · TD17

35

6

Commissioning

6.2

Node address setting

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.2

Node address setting

The POWERLINK node address (node ID) is set via the front DIP switches.

[6-1]

DIP switch

• The labelling on the housing corresponds to the valencies of the individual DIP switches for

determining the node address (Node ID).

• Lenze setting for DIP switches 1 ... 128 = OFF (invalid value "0")
• Valid addresses in the POWERLINK network for the communication module:

• 1 … 100: Controlled node with Lenze module E94AYCEP as managing node
• 1 … 239: Controlled node with managing node of another manufacturer

• The corresponding Ethernet IP address of the communication module results from the address

setting of the DIP switches:
IP address: 192.168.100.[Node ID]

Note!

• Each network node address must only be used once.
• The node address setting in the configuration software (e.g. »Engineer«) and the DIP

switches must be identical for each node.

• Switch the voltage supply of the communication module off and on again to activate

changed settings.

E94YCEP001D