2 powerlink error messages, Powerlink error messages, 9error messages – Lenze E94AYCEC User Manual

Page 61

Advertising
background image

Lenze · E94AYCEC Communication module (POWERLINK CN) · Communication Manual · DMS 3.0 EN · 08/2014 · TD17

61

9

Error messages

9.2

POWERLINK error messages

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.2

POWERLINK error messages

• The POWERLINK error messages are displayed via code

C13910

/

C14910

.

• In order to distinguish between the error responses, the displayed error messages are preceded

with 3 characters:

Response

Meaning

EL_...

Trouble (Fault)

QL_...

Quick stop by trouble

WL_...

Warning locked

I__...

Information (Info)

Error number

Name

Description

hex

dec

0x1

1

EL_ LeaveData

Exchange

The POWERLINK data exchange has been completed (the node

recognises that it does not have the "DataExchange" status

anymore).

Causes & remedy:

• see error description

EPL: DataExchange exited [0x00c88131] ( 58)

Codes:

C13883

/

C14883

(error response)

0x3

3

QL_ LeaveData

Exchange

0x4

4

WL_LeaveData

Exchange

0x6

6

I__LeaveData

Exchange

0x18263 98915

EL_EPL_BOOTUP_1

The Managing Node could not start the POWERLINK network.

OR:

Not all required nodes were found.

Causes & remedy:

• see error description

EPL MN: Network has not been started (bootup-1) [0x00c88263]

( 58)

Codes:

C13891/2

/

C14891/2

(error response)

0x38263 229987

QL_EPL_BOOTUP_1

0x48263 295523

WL_EPL_BOOTUP_1

0x68263 426595

I__EPL_BOOTUP_1

0x18264 98916

EL_EPL_BOOTUP_2

The Managing Node could not transfer all nodes into the

"NMT_CS_OPERATIONAL" status via process data exchange.

Causes & remedy:

• see error description

EPL MN: Not all nodes are in the operational status (bootup-2)

[0x00c88264] ( 58)

Codes:

C13891/2

/

C14891/2

(error response)

0x38264 229988

QL_EPL_BOOTUP_2

0x48264 295524

WL_EPL_BOOTUP_2

0x68264 426596

I__EPL_BOOTUP_2

0x18265 98917

EL_EPL_CN_SYNC_

LOSS

In the Controlled Node, the synchronisation cycle of the Managing

Node has failed. The Controlled Node automatically changes to the

"NMT_xx_PREOPERATIONAL_1" status and waits for a new run-up

by the Managing Node.

Causes & remedy:

• see error description

EPL: Synchronisation lost from MN [0x00c88265] ( 59)

Codes:

C13127/3

/

C14127/3

(monitoring threshold)

C13891/3

/

C14891/3

(error response)

C13127/1

/

C14127/1

(error counter)

0x38265 229989

QL_EPL_CN_SYNC_

LOSS

0x48265 295525

WL_EPL_CN_SYNC_

LOSS

0x68265 426597

I__EPL_CN_SYNC_

LOSS