2 possible causes and remedies, Possible causes and remedies, 0x00c83100 – Lenze E94AYCEC User Manual

Page 56: 0x00c85531, 0x00c85532, 0x00c85533, 0x00c86010, 9error messages

Advertising
background image

9

Error messages

9.1

Error messages of the communication module

56

Lenze · E94AYCEC Communication module (POWERLINK CN) · Communication Manual · DMS 3.0 EN · 08/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.1.2

Possible causes and remedies

In this chapter, all error messages of the communication module are listed in numerical order of the

error numbers. Possible causes and remedies and responses to the error messages are described in

detail.

EPL: Lost connection to 9400 [0x00c83100]

EPL: Memory access error [0x00c85531]

EPL: Memory: Read error [0x00c85532]

EPL: Memory: Write error [0x00c85533]

EPL: Internal watchdog activated [0x00c86010]

Response (Lenze setting printed in bold)

Setting: not possible

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The MXI communication to the Servo Drive 9400 is

interrupted.

• Servo Drive 9400 is switched off.

• The communication module is not connected

correctly at the MXI slot of the Servo Drive 9400.

• Communication module is defective.

• Switch on Servo Drive 9400.

• Plug in the communication module correctly at the

MXI slot of the Servo Drive 9400.

• Send communication module together with a

description of the fault to Lenze.

Response (Lenze setting printed in bold)

Setting: not possible

None  System error  Error  Fault  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Access via the Servo Drive 9400 to a parameter set in the

memory module failed.

Download application again (including module).

Response (Lenze setting printed in bold)

Setting: not possible

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Parameter in the memory module could not be read.

Download application again (including module).

Response (Lenze setting printed in bold)

Setting: not possible

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Parameter in the memory module could not be written. Download application again (including module).

Response (Lenze setting printed in bold)

Setting: not possible

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Communication module is defective.

Send communication module together with a

description of the fault to Lenze.

Advertising